Option 1: Connect to the recorder using AuraServ, then save the file using “File → Save”.
Option 2: Extract from a disturbance recording file in AURA2000 using the command “File → Extract database”.
Option 3 Connect to the network drive, if access is enabled, and download the file "*.dta".
The factory-set address is listed in the factory test report. The program AuraServ can find recorders on the network. If none are detected, disable the antivirus and firewall. Discovery works even when the recorder's address is on another subnet. To establish a connection, however, assign the network adapter an address on the same subnet.
For example, if the recorder has address 169.254.0.22 and subnet mask 255.255.0.0, assign the laptop an address 169.254.x.x, where x is from 1 to 254, avoiding the recorder's address ending in 0.22. The address portions corresponding to 255 in the mask must match, while the host address must be different.
The trigger element picks up at 1.1 A and resets at 0.5 A. Until it resets, the indicator remains lit and cannot be cleared manually. Once the value falls below 0.5 A, the latched indication can be cleared manually. Falling to 1.1 A has no effect, as that is the pickup threshold. The recorder triggers only once when the threshold is exceeded, regardless of how long the triggering condition lasts.
Suppose the pickup and reset thresholds are both set to 1.1 A. If the measured value fluctuates around this threshold, for example between 1.11 and 1.099 A, a new trigger occurs every time it crosses the threshold. A reset ratio prevents this repeated triggering. A 20 ms trigger delay also prevents short interference pulses from triggering the recorder.
If the recorder is retriggered during a disturbance recording—that is, the threshold is exceeded, the signal returns to its original state, and the threshold is exceeded again—the recording timer restarts. For example, with an 8 s recording duration, a retrigger at the fourth second produces a total recording duration of 12 s.
Typically, the following triggers are set for each busbar system:To detect a symmetrical voltage drop, a threshold on one phase is sufficient. This is enough to trigger the recorder for all fault conditions.
For major 500 kV and 330 kV transmission lines, the following additional thresholds are set: