The AURA-AK recorder can contain up to eight replaceable modules, each with four analog and eight binary measurement channels. Modules are available with either current or voltage measurement channels. Current is measured by passing the current-circuit conductor through a ferrite aperture, without adding resistance to the circuit. Voltage and binary circuits connect directly to the module terminals.
Request a quoteThe AURA-AK digital fault recorder is an integrated unit with measuring transducers and binary signal monitoring circuits combined in replaceable modules. It can contain up to eight modules, each with four analog and eight binary measurement channels. Current-input or voltage-input modules are fitted to the customer’s specification.
Current circuits are connected using ferrite rings with an 8 mm internal diameter. Passing the current-circuit conductor through the ferrite ring forms the measuring circuit without adding resistance to the current circuit. Voltage and binary circuits connect directly to the unit terminal blocks, without intermediate terminals.
The central unit housing is made from an aluminum extrusion, providing electromagnetic shielding and the mechanical strength required for long-term industrial operation. Plug-in connections allow functional modules to be replaced quickly when necessary.
The compact recorder measures and monitors normal and fault conditions in power-sector and industrial equipment. It is a cost-effective choice for applications with a relatively small number of monitored channels.
AURA-AK can operate independently as a digital fault recorder or as part of a distributed automated measurement system.
AURA-AK comprises an industrial PC-based central unit, system software, measuring transducers and communication equipment.
AURA-AK variants offer different combinations of current and voltage transducers.
Application software for PC workstations running Windows is included.
The AURA-AK main unit has a vibration-resistant aluminum-profile enclosure for industrial service and contains a fanless single-board computer.
The front panel contains:Windows XP Embedded or Linux operating system.
An AURA-AK transducer module is a replaceable unit containing measuring transducers and binary signal monitoring circuits. The AURA-AK recorder supports up to eight of these modules, each with 4 analog and 8 binary measurement channels. Modules are supplied with either current or voltage measurement channels to the customer's specification.
Current circuits use ferrite rings with an 8 mm internal diameter. Passing the current-circuit conductor through the ferrite ring forms the measuring circuit without introducing additional resistance into the current circuit.
Voltage and binary circuits connect directly to the module terminals without intermediate terminal blocks.
AURA-AK provides connections and galvanic isolation for 64 binary channels. The transducer modules contain optocouplers with a 3000 V isolation rating and binary signal switching circuits. An isolated power supply on the backplane (concentrator) provides the 30 V sensing voltage for binary signals.
The binary signal must be provided by a volt-free contact or a semiconductor device with the required switching current and voltage ratings.
The binary input acquisition module draws 2–10 mA in the closed state with a circuit resistance of up to 500 Ω.
When semiconductor devices generate the binary signal, their residual current in the open state must not exceed 0.1 mA for reliable detection.
The standard disturbance recording duration is 8 s. It can be configured in software over a range of 1–3,600 s.
The pre-fault recording duration is 0.1 s and can be configured in software up to 180 s. COMTRADE recording must be disabled when increasing the pre-fault recording duration.
The maximum intrinsic absolute clock error of AURA-AK without time synchronization signals is 10 seconds per day.
AURA-AK becomes operational within 30 seconds.
AURA-AK provides binary outputs to indicate a recording trigger or device fault. Each output switches a semiconductor solid-state relay between its closed and open states.
AURA-AK requires a 12 V DC ±10% supply. No supply-ripple requirement is specified for DC operation. The power supply arrangement is selected during system design. With suitable AC/DC or DC/DC converters, the recorder can be powered from 220 V ±44 V or 127 V ±25.4 V AC at 50 Hz, or from 220 V ±44 V or 72–144 V DC. For AC supplies, permissible frequency deviations and harmonic content are specified in GOST 13109.
| Number of analog channels | Number of binary channels | Samples per cycle (scanning rate, Hz) |
|---|---|---|
| 4 | 8 | 20…768 (1000…38400) |
| 8 | 16 | 20…384 (1000…19200) |
| 16 | 32 | 20…192 (1000…9600) |
| 32 | 64 | 20…96 (1000…4800) |
AURA-AK power consumption does not exceed 45 W.
The mean time between failures of replaceable AURA-AK components is at least 125,000 hours.
The mean service life of AURA-AK is at least 25 years.
AURA-AK is classified as O4 under GOST 15150 for climatic resistance. The recorder meets the safety requirements of GOST 22261-94 and GOST R 50377-92, the electromagnetic compatibility requirements of GOST R 50839-95 and GOST R 51318.22, and specification TU 4252-020-12325925-2011.
The AURA-AK digital fault recorder is listed in the Russian State Register of Measuring Instruments, registration no. 72492-18.
Accuracy class:
AC current and voltage: 0.5
DC current and voltage — 0.5
phase displacement: 0.5
frequency — 0.05
AURA-AK supports physical quantity transducers with DC output signals, or instantaneous AC current outputs, in the ranges −5…0…5, 0…5, −20…0…20, 0…20, 4…20 and −40…0…40 mA, and 75 mV shunts. Each current-loop analog input has an input resistance of 20 ±5 Ω.
The maximum permissible errors, expressed as a percentage of the reference value, with the input transducers under operating conditions do not exceed:| Designation | Measurement range and unit | |||
|---|---|---|---|---|
| Voltage transducer | ||||
| PN-4~ | 80 V AC | 120 V AC | 160 V AC | 240 V AC |
| PN-4-a | 150 mV–400 V * | |||
| AC current transducer | ||||
| PT-4-10 | 1 A | 2 A | 5 A | 10 A |
| PT-4-200 | 20 A | 40 A | 100 A | 200 A |
* Measurement ranges are set to the customer's requirements
Weight: 3.2 kg.
Disturbance files are stored on the recorder's drive, in the AWR and COMTRADE folders, until deleted.
Files can be deleted in the following ways.Measurements under normal operating conditions are available through IEC 60870-5-104 and an OPC server.
Waveform transmission using IEC 60870-5-104. Data is transmitted spontaneously as soon as the disturbance file is recorded. The analog deadband is 5%. IEC 60870-5-104 timestamps allow signal envelopes to be reconstructed, including phase-angle envelopes.
AURA-AK with its measuring transducers provides: