Portable Digital Fault Recorder (DFR)

The TransAURA recorder is a single integrated unit mounted in a carrying case. Its enclosure incorporates removable input measuring transducers and a binary input unit. TransAURA is supplied with input connection cables and current clamps. It can record disturbances and normal operating conditions or serve as a multichannel voltage, current and phase-angle meter.

Request a quote

The TransAURA digital fault recorder is based on an industrial computer. Its circuit design, embedded software and functions are equivalent to those of AURA recorders.

Design

The recorder is a single integrated unit mounted in a carrying case, with compartments for measurement cables and current clamps. Its enclosure incorporates removable input measuring transducers and a binary input unit. Input connection cables and current clamps are included.

The recorder is a single integrated unit mounted in a carrying case, with compartments for measurement cables and current clamps. Its enclosure incorporates removable input measuring transducers and a binary input unit. Input connection cables and current clamps are included.

TransAURA includes an industrial-computer-based main unit, system software, measuring transducers and communication equipment.

TransAURA variants offer different combinations of current and voltage transducers, with a maximum of 16 transducers.

The standard TransAURA configuration includes:
  • one N-0.6 DC and AC voltage transducer;
  • 3 N-250 AC/DC voltage transducers;
  • 4 NP-120 AC voltage transducers;
  • 8 T-2000 AC current transducers;
  • 4 Q8A2 current clamps;
  • four XQ20 current clamps.

Application software for PC workstations running Windows is included.

The TransAURA recording unit has an industrial, vibration-resistant aluminum extrusion enclosure and a single-board computer with fanless cooling.

The front panel contains:
  • LED indicators;
  • buttons for switching the recorder on and off, triggering a test recording and resetting alarms;
  • binary input connectors;
  • analog transducer modules;
  • a connector for the 220 V DC supply cable;
  • the processor board connection panel for external devices.

The operating system is based on the Linux kernel.

The voltage input transducers accept both AC and DC signals. Each analog voltage channel has an input impedance of no more than 20 kΩ. Current is measured using current clamps connected to the current transducer inputs.

The N-0.6 transducer can measure current through a shunt.

The recorder accepts two-state binary signals from volt-free contacts or solid-state switching devices. It connects and galvanically isolates 32 binary channels.

Recorder specifications
  • Number of analog channels 2–16
  • Number of binary channels 32
  • Channel sampling rate: 20–320 samples per cycle (1000–64000 Hz) for 16 channels; 20–1280 samples per cycle for four channels
  • ADC resolution 12 bits
  • Triggers: any analog or binary channel, calculated U2
  • Power supply 220 V DC, 220/127 V AC
  • Storage: flash drive, 240 GB minimum
  • Communication: 10/100/1000 Mbps Ethernet
  • Operation and maintenance: from a laptop or desktop computer over the network.

The TransAURA digital fault recorder is listed in the Russian State Register of Measuring Instruments, registration no. 72492-18.

Transducer specifications:

The binary input circuit draws 2–10 mA with a line resistance of up to 500 Ω. Isolation voltage is 3,000 V. Binary channels are powered from a galvanically isolated 24 V supply.

Transducer measurement ranges
Type Ranges (software-selectable)
T-2000 current transducer 1 A AC 2 A AC 5 A AC 10 A AC
10 A AC 20 A AC 50 A AC 100 A AC
20 A AC 40 A AC 100 A AC 200 A AC
100 A AC 200 A AC 500 A AC 1000 A AC
200 A AC 400 A AC 1000 A AC 2000 A AC
N-0.6 DC and AC voltage transducer 0.105 V DC 0.21 V DC 0.42 V DC 0.84 V DC
0.075 V AC 0.15 V AC 0.3 V AC 0.6 V AC
N-120 AC/DC voltage transducer 21 V DC 42 V DC 84 V DC 168 V DC
15 V AC 30 V AC 60 V AC 120 V AC
N-250 DC and AC voltage transducer 43.75 V DC 87.5 V DC 175 V DC 350 V DC
31.25 V AC 62.5 V AC 125 V AC 250 V AC
NP-120 AC voltage transducer 15 V AC 30 V AC 60 V AC 120 V AC

Weight: 16 kg.

TransAURA overall and mounting dimensions
The following options can be supplied on request:
  • desktop or laptop computer;
  • cellular, radio or DSL modem;
  • additional transducers, up to a total of 16 in the recorder;
  • additional current clamps rated at 10 A, 100 A, 200 A, 1000 A and 2000 A.

TransAURA recorder order specification form

Number of recorders __________
Input transducer kit for each recorder

No. Transducer type Quantity
     

Order prepared by _____________________________________________
  Signature / Printed name

(Date)

Completed example
No. Transducer type Quantity
1 N-0.6 4
2 N-120 4
3 T-2000 (100 A) with current clamps 4
4 T-2000 (200 A) + current clamps 4
  1. Disturbance recording: generation of a single disturbance file or a series of files, depending on the trigger conditions;
  2. recording binary state changes by creating files listing the binary channels that changed state during the day;
  3. normal-condition recording: measurement files for normal operating channels, sampled every 5–180 seconds;
  4. the device can serve as a recorder of normal operating and fault conditions or as a multichannel volt-ampere-phase meter.