SPC digital measuring transducers digitize AC current, voltage, power and frequency signals in three-phase, three-wire and four-wire electrical circuits. SPC units also convert measured quantities into ±5 mA DC signals and process binary signals from volt-free contacts.
Request a quoteSPC digital measuring transducers convert AC current, voltage, power and frequency measurements in three-phase, three-wire and four-wire circuits into digital data.
SPC units also convert measured quantities into ±5 mA DC signals and process binary signals from volt-free contacts.
The transducers are housed in plug-in plastic enclosures. The cover is secured to the connector section with four screws and has two latches that lock the transducer into its mating connector. The input connector is similar to a conventional BI-6 test block. It shorts the current circuits when the transducer is withdrawn and permits current-injection testing and insulation testing of incoming cables. Guide ribs between connector contacts prevent short circuits if the transducer is accidentally tilted during insertion. The mating connector has M4 screw terminals for the input and output circuits.
automated monitoring and control systems, SCADA systems, and automated electricity metering and monitoring systems at power utilities and other industrial facilities.
| Designation | Nominal input ratings | Connection diagram | |
|---|---|---|---|
| Current, A | Voltage, V | ||
| SPC-100/1-4 | 3 × 1 | 3 × 57.7 | Four-wire |
| SPC-100/1-3 | 2 × 1 | 3 × 100 | Three-wire |
| SPC-100/5-4 | 3 × 5 | 3 × 57.7 | Four-wire |
| SPC-100/5-3 | 2 × 5 | 3 × 100 | Three-wire |
| SPC-380/5-4 | 3 × 5 | 3 × 220 | Four-wire |
| SPC-x/x-x | SPC-x/x-x-T2 | SPC-x/x-x-T3 | |
|---|---|---|---|
| AC supply: 187–253 V | + | + | + |
| Universal power supply 120–370 V DC or 90–264 V AC | - | + | + |
| Current outputs ±5 mA (±20 or 4–20 mA on request) | - | - | 3 units |
| Inputs for four volt-free contacts | 4 | 4 | 4 |
| Volt-free contact sensing voltage | 30–48 V | 30 V | 30 V |
SPC-100/5-4-T3 | | | | |_____ additional options | | | |________ SPC measurement circuit connection | | | 3 — three-wire | | | 4 — four-wire | | |__________ rated input current | | 1 — 1 A | | 5 — 5 A | |_____________ rated line-to-line input voltage | 100 — 100 V (57.7 V phase-to-neutral for four-wire connection) | 380 — 380 V (220 V phase-to-neutral for four-wire connection) |_________________ device type
SPC units support three communication protocols, IEC 870-5-1-95 (FT3), IEC 60870-5-101 and MODBUS.
The protocol is specified when ordering and configured in software.
Measurement update interval: no more than 400 ms.
When ordering transducers with current outputs, specify the measured quantity assigned to each output and its full-scale value corresponding to 5 mA. If current output settings were not specified when ordering, configure them with the service program before commissioning.
| Parameter | Value |
|---|---|
| Ambient air temperature, °C | 0…+55 |
| Relative humidity, % | 30…80 |
| Atmospheric pressure, kPa | 84…106 |
SPC-xxx/x-x transducers have a standard supply voltage range and can be powered from an AC supply.
| Parameter | Value |
|---|---|
| Supply frequency, Hz | 45…55 |
| AC supply voltage, V | 187…253 |
SPC-xxx/x-xT2 and SPC-xxx/x-xT3 transducers accept a wider supply voltage range and can operate from AC or DC supplies.
| Parameter | Value |
|---|---|
| Supply frequency, Hz | 45…440 |
| AC supply voltage, V | 90…264 |
| DC supply voltage, V | 120…370 |
Supply power consumption does not exceed 7 VA.
| Parameter | 4-wire connection | Three-wire connection |
|---|---|---|
| Phase-to-neutral voltage on each phase | yes | no |
| Phase current in phases A and C | yes | yes |
| Phase current in phase B | yes | no |
| Line-to-line voltages AB and BC | yes | yes |
| Line-to-line voltage A–C | yes | yes |
| Active power for each phase | yes | no |
| Total three-phase active power | yes | yes |
| Reactive power for each phase | yes | no |
| Total three-phase reactive power | yes | yes |
| Apparent power per phase | yes | no |
| Average line-to-line voltage | yes | yes |
| Average phase-to-neutral voltage | yes | no |
| Average three-phase current | yes | yes |
| Power frequency | yes | yes |
| Input current and voltage phasor angles | yes | yes |
Voltage and current measurements are RMS values.
SPC units with four-wire connections calculate line-to-line voltages from phase-to-neutral voltages.
| Parameter | SPC-100/5-X-XX | SPC-100/1-X-XX | SPC-380/5-X-XX | SPC-380/1-X-XX | ||||
|---|---|---|---|---|---|---|---|---|
| range | nominal | range | nominal | range | nominal | range | nominal | |
| Phase-to-neutral voltage, V | 0-69,3 | 57,735 | 0-69,3 | 57,735 | 0-264 | 220 | 0-264 | 220 |
| Phase current, A | 0-6 | 5 | 0-1,2 | 1 | 0-6 | 5 | 0-1,2 | 1 |
| Line-to-line voltages, V | 0-120 | 100 | 0-120 | 100 | 0-456 | 380 | 0-456 | 380 |
| Active power per phase, W | 415,6 | 288,68 | 83,1 | 69,282 | 1584 | 1100 | 316,8 | 220 |
| Total active power, W | 1247 | 866,03 | 250 | 173,205 | 4752 | 3300 | 950,4 | 660 |
| Phase reactive power, var | 415,6 | 288,68 | 83,1 | 69,282 | 1584 | 1100 | 316,8 | 220 |
| Total reactive power, var | 1247 | 866,03 | 250 | 173,205 | 4752 | 3300 | 950,4 | 660 |
| Power frequency, Hz | 47,5-52,5 | 50 | 47,5-52,5 | 50 | 47,5-52,5 | 50 | 47,5-52,5 | 50 |
| Measured quantity | Maximum permissible intrinsic error as a percentage of the reference value |
|---|---|
| Phase current, I | ±0,3 |
| Voltage, U | ±0,3 |
| Active power, P | ±0,5 |
| Reactive power, Q | ±0,5 |
| Frequency, F | ±0,03 |
| ±5 mA DC outputs | ±0,15 |
SPC-xxx/x-x, SPC-xxx/x-x-T2 and SPC-xxx/x-x-T3 units acquire, process and transmit binary status signals from volt-free contacts. SPC-xxx/x status input circuits have an isolated 30–60 V power supply; SPC-xxx/x-x-T2 and SPC-xxx/x-x-T3 units use 27–33 V. Closed-circuit current depends on circuit resistance and is typically 5–10 mA.
SPC-xxx/x-x-T3 units have isolated ±5 mA DC outputs that can represent any measured quantity. Factory current output settings are listed in the product data sheet.
SPC current and voltage measurement circuit burden at rated current and rated frequency does not exceed the following values.| Parameter | Exposure duration |
|---|---|
| Input voltage with a peak value of 500 V | continuous |
| 200 A pulse input current | no more than 1 s |
| Parameter | Value |
|---|---|
| RS-485 communication rate | 1200, 9600, 19200 or 57600 baud |
| Built-in surge protection on RS-485 circuits | 15 kV under IEC 61000-4-2 |
| Analog measurement update interval | 0.4 s |
| Binary status update interval | 1 ms |
| Measurement timestamp accuracy | up to 1 ms |
| Maximum time from request receipt to start of data output | 2 ms |
Weight 0.7 kg.
Weight 7.6 kg.