SCADA with an RTU

AURA-KP comprises a data acquisition and communication unit and digital measuring transducers distributed throughout the site. An industrial computer serves as the central unit, while SPC units or other devices with open communications protocols provide the measurements. Transducers connect through serial/RS-485, USB/RS-485 or Ethernet/RS-485 converters. digital fault recorders can also connect to the central unit over Ethernet if required (Figure 1). Data sources can be connected using IEC 60870-5-104 or an OPC server.
Measurements in the data acquisition and communication unit are continuously updated by cyclically polling the transducers. Data is transmitted to higher-level systems over communication links using IEC 60870-5-101, over Ethernet using IEC 60870-5-104, and over the Internet using HTTP. Data can also be supplied through an OPC server.

Figure 1

Measurement channel redundancy (Figure 2) is provided by connecting standby transducers to the data acquisition and communication unit through standby interface converters and communication lines. Standby connections are polled continuously, just like the primary connections. If a primary channel fails, the standby channel’s values replace it, with the substituted quality flag transmitted over IEC 60870-5-101 and IEC 60870-5-104.

Figure 2

Data acquisition and communication unit redundancy (Figure 3) uses a measuring transducer network and two main units. Ethernet/RS-485 interface converters connect to the transducers. The two units communicate over Ethernet and a direct COM-port cable. When the first unit starts and detects no partner, it becomes the active unit and connects to the transducers. When the second unit starts and detects its partner, it becomes the standby unit and connects to the active unit. Channel lists are synchronized, and the standby unit receives all data from the active unit.
If both Ethernet and direct-cable communication with the active unit are lost, the standby unit becomes active and connects to the measuring transducers. When the original active unit recovers, it operates as the standby.

Figure 3
SCADA systems using an AURA-KP server
SCADA server communicating with three destinations